Use the following table to set the values in the Device Manager and NI MAX.
ACTUATOR NAME | WIN 10 DEVICE MANGER | NI USB-485 | NI MAX | ||||||
COM # | BAUD | PARITY | STOP BIT | FLOW CTRL | TRANSCEIVER | BIAS RESISTOR | PORT | ALIAS | |
Caliper |
7 | 19200 | EVEN | 1 | NONE | 2-Wire Auto | YES | 1 | CALIPER |
Y Bayonet | 6 |
19200 | EVEN |
1 | NONE | 2-Wire Auto | YES | 2 | Y-BAYONET |
Z Bayonet |
9 |
19200 | EVEN |
1 | NONE | 2-Wire Auto | YES | 3 | Z-BAYONET | ||||
n/a | n/a | n/a | n/a | n/a | n/a | n/a | n/a | 4 | n/a |
Info |
---|
The Expert software does not use or care about the NI MAX alias names but they are critical the LabVIEW application. |
...