Data communication and control is USB based and managed via National Instrument's Measurement & Automation Explorer (NI-MAX). When you open NI-MAX and expand the Device and Interface section it should appear as seen to the right. On the following pages is an edited version of the NI-MAX report. Text in italics are additional comments for context. To have a pain free experience use these parameters and follow the advice.
The technician should fully understand how to use this information and setup the hardware.

Image RemovedImage Added

MAX Configuration Report

11

08/

19

30/

2018 10

2022 8:

44

07:

37

16 AM

Devices and Interfaces

  • NI USB-485 Interface "RS-485 SN:00DCF18B"

1:ASRL3::INSTR "X-AXIS"

NI USB-485 Interface "RS-485 SN:00DCF18B"

This is a single port USB to RS-485 serial device. With this device we connect to the M-Drive interface board.
It is extremely important that the alias name "X-AXIS" is used. This is the means by which IMS knows which USB is connected to the M-Drive that moves the X-axis (sample handler).
Also, be aware that if you change the USB to 485 cable NI-MAX will know. Each cable has a serial number. You will have to delete any previous alias names and reassign them to the correct serial ports. You must also reset the serial port communication parameters.

1: ASRL3::INSTR "X-AXIS"

  • Name X-AXIS
  • Slot Number 1
  • Port Binding COM3
  • Port Description
NI USB-485/1 SN:00DCF18B, Communications Port
  • Unknown
  • VISA Resource NameASRL3::INSTR
  • Port Settings
    • Baud
rate9600
    • rate 9600
    • Data bits8
    • Parity None
    • Stop bits1
    • Flow
controlNone
    • control None


Property Value

  • Resource Name ASRL3::INSTR
  • Device Type Serial Port
  • VISA Alias on My
SystemX
  • System X-AXIS
  • Device Enabled True

Link to Word Version:NGR NI Max setup.docx (not updated!)
















  • Prior to KTLF 397P computer replacement the port description was NI USB-485/1 SN:00DCF18B, Communications Port